General
Maximum voltage between any voltage terminal and earth ground
1000 V
Maximum voltage between any current terminal and earth ground
30 V
Safety
General
IEC 61010-1: pollution degree 2
Measurement
IEC 61010-2-030: CAT IV 600 V / CAT III 1000 V
Dimensions
Outside
148 mm x 187 mm x 23 mm (W x H x D)
(148 mm x 370 mm x 19 mm with cover opened)
Inside
140 mm x 158 mm x Di (W x H x D)
Di = 58 – thickness of panel door in mm
Supported electrical enclosures
Enclosure
UL 50/NEMA environmental type 1 (Type 12 when PQ400 cover is closed)
Panel thickness
Max. 3.5 mm (10 gauge)
Environment
Operating/storage temperature
-25 °C to 60 °C
Humidity
10 % to 90 % in dependency of temperature according to IEC 60721-3-3 Class 3K6 (modified):-25 °C to 35 °C: 10 % to 90 %, 50°C: max. 35 %, 60°C: max. 23 %
Altitude
Operating
2,000 m (up to 4000 m derate to CAT II 1000 V, CAT III 600 V, CAT IV 300 V)
Ingress protection
Rating
IEC 60529: IP67 with cover closed, IP50 with cover opened and all connectors attached
Vibration
IEC 60068-2-6 , MIL-PRF28800F: Random vibration class 2
Voltage
Number of inputs
5 (A/L1, B/L2, C/L3, N, and earth/ground)
Wire gauge
Solid/flexible: 0.25 mm2 to 1.5 mm2 (AWG 24 to AWG 16)
Fuse
2 A 1000 V 1.5 A²s, 10 kA IR (A/L1, B/L2, C/L3, N)
Connectors
5x 4 mm safety terminals, 3x red for A/L1, B/L2, C/L3, 1x black for N, 1x green for earth/ground
Current
Connectors
5x 4-pin circular compatible with Fluke 354x FC, 173x, and 174x power and power quality loggers (these loggers can all be power from the measured voltage up to 500V)v